Previous Article Next article Return to overview
Tubular Cell Electrolysis Plants CHLORINSITU® II

Tubular Cell Electrolysis Plants CHLORINSITU® II

Electrolysis plants of the types CHLORINSITU® II produce sodium hypochlorite with a concentration of 5 g/l. For this process, a saturated solution of sodium chloride is produced in a salt dissolving tank included in the scope of delivery. This solution is then diluted correspondingly and electrolysed in a membrane-free cell. The resulting solution is collected in a storage tank and from there metered with separate metering pumps as needed. Because of the moderate pH value of approx. 9, the pH value of the treated water is significantly less affected than when using commercially available sodium hypochlorite (pH 12-13.5). The generated hydrogen is diluted with fresh air through an ATEX-certified ventilator and discharged safely. Both the salt dissolving and the diluent water come from a softener integrated in the plant. Thus, lime deposits can be prevented and a long service life of the electrolytic cell can be ensured.

The plants are controlled with a modern PLC with large, illuminated display and integrated modem for remote diagnosis and troubleshooting.


Advantages

  • Robust, simple technology
  • Compact, space-saving design
  • Safe plant control with remote diagnosis via modem
  • Economic operation thanks to the inexpensive raw material sodium chloride and less chemical consumption for pH value adjustment

Application areas 

  • specifically suitable for applications where a robust and clearly arranged technology is required, and where an entrainment of sodium chloride into the water to be treated has no influence


Features

  • Electrolysis plant mounted ready for operation on a powder-coated stainless steel frame with programmable logic controller (PLC) in control cabinet
  • integrated softener
  • electrolytic cell
  • ATEX-certified bleeding system and side salt dissolving tank with level monitor
  • Level sensors to monitor the storage tank for sodium hypochlorite to be provided by the customer
  • Automatic monitoring of the water hardness downstream of the softener and chlorine gas detector for plants from 600 g/h

Technical Data

Type/
Output





[g/h]
Voltage   
Supply
Power
Uptake





[kW]
Salt Con-sumption 





[kg/h]
Process
Water Con-sumption




[l/h]
Dimensions
L x W x H





[mm]
Brine
Tank





[l]
Recom- mended
Capacity Storage
Tank


[l]
50  3 x 400 V  0.78  0.2  11  1050x600x1550  80  300
100  3 x 400 V  1.15  0.4  22  1050x600x1550  80  500
150  3 x 400 V  1.53  0.6  32  1050x600x1550  200  700
200  3 x 400 V  1.90  0.8  43  1050x600x1550  200  1000
300  3 x 400 V  2.65  1.1  65  1050x600x1550  200  1500
400  3 x 400 V  3.40  1.5  86  1500x800x2000  200  2000
500  3 x 400 V  4.15  1.9  108  1500x800x2000  380  2500
600  3 x 400 V  4.90  2.3  129  1500x800x2000  380  3000
800  3 x 400 V  6.40  3.0  172  1500x800x2000  380  3500
1000  3 x 400 V  7.90  3.8  215  1500x800x2000  520  4500
1200  3 x 400 V  9.40  4.6  258  1500x800x2000  520  5500
1400  3 x 400 V  10.90  5.3  301  1500x800x2000  520  6000
1600  3 x 400 V  12.40  6.1  344  1500x800x2000  520  7000