Single-Channel Measuring and Control Instrument DULCOMETER® Type D1Cb/ D1Cc

Single-Channel Measuring and Control Instrument DULCOMETER® Type D1Cb/ D1Cc

A safe, comfortable, and clear operation is guaranteed thanks to the large, illuminated graphic display, full text operating menu in 15 operating languages, and pH sensor monitoring.

  • Always the appropriate controller:
    Both sensor connection types mA and mV in one single unit
  • Subsequent activation of functions via activation key
  • For connection type standard signal:
    all other measured variables such as chlorine, bromine, chlorine dioxide, chlorite etc. and pH, ORP/Redox and conductivity via mA
  • For mV: switching capability between pH and ORP/Redox
  • Plain text user guidance in 15 operating languages in the controller
  • Control of 2 metering pumps via pulse frequency
  • 2 power relays for solenoid valve control, limit value monitoring or timer function
  • Large, illuminated graphic display with bargraph
  • 1 analogue output 0/4 … 20 mA (measured value/controller output)
  • Extended range voltage supply: 90-253 V, 50/60 Hz
  • Automatic buffer recognition for pH
  • pH sensor monitoring
  • Calibration timer, calibration log book
  • Operating hours counter
  • Metering time monitoring with deactivation of the controller output if time is exceeded

Application focuses

  • Drinking water treatment
  • Waste water treatment
  • Cooling water treatment
  • Boiler feed water treatment
  • Neutralisation

Technical Data

Size

Value

Measurement Range

Type of Connection: mV:
pH: 0.00 to 14.00
ORP: -1.000 to +1.000 mV
Type of Connection mA: Chlorine, Chlorite, Bromine, Ozone, Hydrogen Peroxide, Peracetic Acid, Dissolved Oxygen, pH, ORP, Conductivity, Temperature

Resolution

pH: 0.01 pH
ORP: 1 mV
Amperometric: 0.001/0.01 ppm, 0.01 vol. %
Accuracy 0,5 % of Measurement Range
Measurement Input SN6 (input resistance  >0,5 x 10^12 Ω)
Correction Variable Temperature via Pt 100/Pt 1000
Correction Range 0 to 100 °C
Disturbance Signals -
Control Charateristic P/PID- Control
Control 2-way Control
Signal Current Output

1 x 0/4-20 mA galvanically isolated max. load 450 Ω,
Adjustable range and allocation (measurement variable, correction variable, controlled variable)

Control Outputs

2 pulse frequency outputs for metering pump actuation
2 relays (limit value or pulse length)
1 x 0/4 to 20 mA

Alarm Relay 250 V ~ 3 A, 700 VA changeover contact
Electrical Connection 90 -253 V, 50/60 Hz,
Ambient Temperature Wall mounting: -5 bis 50°C
Enclosure Rating Wall mounting: IP 65;
Schaltafeleinbau: IP 54
Dimensions Wall mounting: 198 x 200 x 76 mm (WxHxD) (D1Cb)
Schalttafeleinbau: 96 x 96 x 145 mm (WxHxD) (D1Cc)

A complete measuring station comprises the following

  • Measuring transducer / controller D1Cb
  • Sensor
  • Fitting: DGMa…, DLG III…, immersion assembly
  • Temperature sensor Pt 100 or Pt 1000
  • Sensor cable
  • Buffer solution
  • Photometer