The cooling tower controller DULCOMETER® Cool-Control is a measuring and control device based on microprocessor technology offering the highest degree of processing reliability in a broad spectrum of applications. The controller is configurable and so can be individually adapted to your requirements. You choose and pay for what only you need.
Advantages
- Optimum adaptation to processing requirements through different levels of configuration
- Seamless integration into your processing technology: Variable installation options for sensors and different control options for dosing equipment together with blowdown shutter valves and valves.
- Safety: Threshold value monitoring and adjustable maximum duration of blowdown
- Simple and easy-to-view user guide in full text via a large graphic display in many languages
- Large, easy-to-read graphics display for measured values, correcting values and information.
Areas of application
- Cooling tower
- Air washers
- Air humidifiers in climatic engineering
Features
- Blowdown control
- Dosing of a corrosion inhibiting agent
- Dosing of 1 or 2 biocides
- Daily and 2-weekly timer
- Forced blowdown and blowdown shutoff
- Calibration function for the dosing pumps
- Water meter input with adjustable pulse spacing
- Pause input for blowdown shutoff
- Signal output for temperature-compensated conductivity, 0/4 – 20 mA, galvanically separated
- Alarm relay for alarm output
- Adjustable alarm threshold for the measured value of conductivity
- Wall and panel mount housing
- Adjustable access code
ProMinent besides offering DULCOMETER measurement devices and controllers also offers DULCOTEST fluid conduction sensors and dosing pumps to build a complete closed loop. Measurement, control, dosage and recording, all from one source and optimised to work together.
Technical Data
| Measurand |
Measurement and Control Range |
Resolution |
Measured Input |
|
Conductive conductivity |
0 - 20 µS/cm 0 - 200 µS/cm 0 - 2 mS/cm 0 - 200 mS/cm |
0,001 µS/cm |
Terminal conductive capacity |
| Inductive conductivity |
0 - 200 µS/cm 0 - 2 mS/cm 0 - 200 mS/cm 0 - 2000 mS/cm |
0,01 µS/cm |
Terminal inductive capacity |
| Size |
Value |
| Accuracy |
0,5 % of the measurement range at 25°C |
| Correction variable |
Temperature via Pt 100 |
| Correction range |
0...100°C |
| Control |
Blowdown between two threshold values with forced blowdown prior to biocide dosing |
| Adjustable outputs |
1 Reed contact for biocide 1
1 Reed contact for corrosion inhibitor
1 power relay for biocide 21 power relay for blowdown valve
or
1 Reed contact for biocide 1
1 Reed contact for corrosion inhibitor
1 adjustable motor output for blowdown valve |
| Analogue outputs |
1 analogue output (0/4…20 mA) galvanically separated, max load 600 W) as measured value |
| Alarm relay |
250V ~3 A, 700 VA, changeover contact type |
| Electrical connection |
24 V AC/DC / 115 V~ /230 V~ ±10% |
| Protection class |
Wall mounted: IP 65
Panel mounted: IP 54 |
| Ambient temperatures |
Wall mounted: -5..0.40°C (non-condensing)
Panel mounted: 0..0.40oC (non-condensing) |
| Dimensions in mm (WxHxD) |
Panel mounted: 96 x 96 x 140
Wall mounted: 189 x 200 x 76 | |