Controller SlimFLEX 5a, the entry-level class for cooling water treatment, VDI 2047 Sheet 2 and BIMSchV 42-compliant, the innovative and flexible controller.
The SlimFLEX5a records all the important measuring parameters for cooling water treatment and controls functions necessary for smooth operation:
- Time-dependent biocide metering (boost metering). Checks can be undertaken by measuring the ORP voltage in the cooling water.
- Measurement of electrolytic conductivity – controls bleeding.
- pH measurement with integrated PID controller Controls processes automatically to ensure that the specified values (e.g. pH: acid or alkaline) are maintained even in the event of interfering influences. more in the glossary.
Your benefits
- A web interface for device configuration and remote maintenance is standard, Wi-Fi is available as an option
- Forced bleeding: performs bleeding before biocide metering
- Bleed lock: blocks bleeding after biocide metering has taken place
- Operating status displayed by 6 status LEDs
- Connection to the DULCONNEX IIoT solution, developed by ProMinent.
Field of application
The following list of applications are general examples of generally suitable applications for this product. Please contact your local sales representative to talk about the applicable use of this product in your specific case / environment.
- Control of bleeding in smaller evaporation cooling systems
- Volume-proportional control or regulation of the metering of corrosion inhibitors, de-foamers and dispersants
- Measurement and if necessary control of pH
- Time-dependent metering of up to 2 biocides
Technical Details
- 6 digital inputs for contact water meter, flow detector and control signals
- 6 status LEDs display the operating status
- 5 flexible relay outputs: for setpoint-dependent flow volume-proportional or time-based control of actuators
- Measured variables: Conductivity, pH, ORP
Technical Data
Measuring range | Conductivity: 10 ... 10,000 µS/cm pH: 0.00 ... 14.00 Redox potential: -1500 ... +1500 mV |
Resolution | Conductivity: 1 µS/cm pH: 0.01 Redox potential: 1 mV Temperature: 0.1 °C |
Inputs and outputs | 2 plug-in module slots: Plug-in modules for 2-channel modules: mA outputs, pH/ORP inputs 5 output relays used as a changeover contact, 3 of which are potential-free and 2 are AC/DC 1 serial sensor input for CTFS sensor 6 digital status inputs |
Accuracy | 0.3% based on the full-scale reading |
Measurement input | pH/ORP (input resistance > 0.5 x 1012 Ω) |
Temperature compensation | Pt 100/Pt 1000 for pH |
Correction range temp. | 0 … 100 °C |
Control characteristic | P/PID control |
Electrical Connection | 100 – 230 V, 50/60 Hz, 25 VA |
Ambient temperature | 0 ... 50 °C (for use indoors or with a protective enclosure) |
Enclosure rating | Wall-mounted: IP 65 |
Tests and approvals | CE, MET (corresponding to UL as per IEC 61010) |
Housing material | PPE with flame-proof finish |
Dimensions H x W x D | 220 x 250 x 122 mm |
Climate | Permissible relative humidity: 95 %, non-condensing DIN IEC 60068 –2-30 |
SlimFlex SF5a with LAN (including cable) and Wi-Fi. Conductive conductivity with CTFS sensor
| Control input | Order no. |
---|
SF5A006W0XXXXXXXXXXXX00000001 | Conductivity (CTFS sensor) | 1095464 |
SF5A006W0XXXXXXH1XXXX00000001 | Conductivity (CTFS sensor), 2 mA outputs | 1095443 |
SF5A006W0XXXXXXXXV2XX00000001 | Conductivity (CTFS sensor), pH/ORP | 1095465 |
SF5A006W0XXXXXXH1V2XX00000001 | Conductivity (CTFS sensor), pH / ORP, 2 mA outputs | 1095466 |
Please order sensors separately.
Service Unavailable